ChipFind - документация

Электронный компонент: APTDINAV53G321

Скачать:  PDF   ZIP
Specifications are subject to change without notice APT-DIN 3 DS0603
1
Measurement of: kW
9 selectable full-scales
in 9 intervals from 0 to 5 (range from 0,4kW to 3,6kW)
Degree of protection (front): IP 50
3 analogue outputs (0 to 10VDC)
Response time:
50ms
Product Description
Model
Range code
System
Power supply
Rated outputs
Number of inputs
Calibration
Ordering Key
APT-DINAV53G3 2 1
Active power
transducer
with auxiliary power sup-
ply of 400VAC (phase-
phase connection). 9 mea-
suring ranges selectable in 9
intervals from 0 to 5 (measur-
ing range from 0,4 to 3,6kW)
The house is for DIN-rail
mounting
and ensures a
degree of protection (front)
of IP 50.
Energy Management
3-channel Power Transducer
Type APT-DIN
Type Selection
System
3:
Three phase system
(3 wires, balanced/
unbalanced load)
Range code
AV5:
400 VAC - 5,2 AAC
(max. 480 V (L-L) -
6,2 A) (standard)
Power supply
D:
230VAC 15+10%
50/60Hz
G:
400VAC 15+10%
50/60Hz
Rated outputs
3: 3 x (0 to 10VDC)
Number of inputs
2:
2 x (3-phase inputs)
Calibration
1 :
3600W.
Rated inputs
2 (3-phase inputs) for current
and voltage measurements
Accuracy
Active power
(@ 25C 5C, R.H.
60%)
3% rdg (cos
0.7 L/C,
0.5 to 1Ph)
Additional errors
Humidity
< 0.5%, 60% to 90% R.H.
Input frequency
< 0.5%, 50 to 60 Hz
Magnetic field
< 0.5% @ 400 A/m
Ripple
balanced load:
1% accor-
ding to IEC 60688-1 and
EN 60 688-1
unbalanced load:
5%
Measurement
kW
Ranges (impedances)
AV5:
400VAC (
2W per channel)
5.2AAC (
0.3 VA per channel)
Frequency range
48 to 62 Hz
Over-load protection
Continuous: voltage/current
1.2 x rated input
For 1 s
Voltage:
2 x rated input
Current:
20 x rated input
Input Specifications
Analogue outputs
Number of outputs
3 (one per channel)
Range
0 to 10 VDC
Response time
50 ms typical
Temperature drift
500 ppm/C
Load:
10 V output
10 k
Analogue outputs
Insulation
By means of optocouplers,
2000 V
rms
output to
measuring input /
power supply
Output Specifications
2
APT-DIN 3 DS0603 Specifications are subject to change without notice
Dimensions
Front Panel Description
1
1. Rotary switch
9-position rotary switch for input full scale selection (at
every selected input full scale correspond a 10VDC output) .
2. LED
Power-ON.
3. Connection terminal blocks
4. Connection terminal blocks
2
3
4
Wiring Diagrams
Three-phase, 3-wire ARON input connections - Unbal-
anced loads
CT connection (3-wire system)
Operating temperature
-20 to +60C (4 to 140F)
(R.H. < 90% non-condensing)
Storage temperature
-30 to +80C (22 to 176F)
(R.H. < 90% non-condensing)
Insulation reference voltage
300 V
rms
to ground
(with neutral connection),
CAT II (double insulation),
CAT III (main insulation)
Pollution degree 2
Insulation
4000 V
rms
between all inputs/
outputs to ground
Dielectric strength
4000 V
rms
for 1 minute
Noise rejection
CMRR
100 dB, 48 to 62 Hz
EMC
EN 50081-1, EN 50082-1
Safety standards
Safety requirements:
IEC 61010-1, EN 61010-1
Products requirements:
IEC 60688-1, EN 60688-1
Connector
Screw-type,
max. 4 mm
2
wires
Housing
Dimensions
115 x 76 x 100 mm
Material
ABS, self-extinguishing: UL94 V-0
Degree of protection
Front: IP50
Weight
Approx. 810 g
(packing included)
General Specifications
APT-DIN
AC voltage
400 VAC (standard),
-15%+10% 50/60 Hz
230VAC (optional)
15+10% 50/60Hz
Power consumption
7 VA
Supply Specifications