ChipFind - документация

Электронный компонент: CPTDIN

Скачать:  PDF   ZIP
Specifications are subject to change without notice CPT-DINBDS190606
1
Class 2 (active energy)
Class 3 (reactive energy)
Accuracy 0.5 F.S. (current/voltage)
Compact Power transducer
Instantaneous variables data format: 4 digit
Energies data format: 8+1 digit
System variables and phase measurements: W, W
dmd
,
W
dmd max
, var, VA, VA
dmd
, PF, V, A, An, A
dmd
, A
max
, A
dmd max
, Hz
Energy measurements: kWh and kvarh
Hour counter (5+2 DGT)
TRMS meas. of distorted sine waves (voltages/currents)
Power supply: 90 to 260VAC/DC and 18 to 60VAC/DC
Protection degree (front): IP20
Dimensions: 45x83.5x98.5mm
RS422/485 serial port
Product Description
3-phase compact power
transducer. Particularly rec-
ommended for the measure-
ments of the main electrical
variables.
Housing for DIN-rail mount-
ing, protection degree IP20
as standard, and RS485 or
RS232 serial port.
Parameters programmable
by means of CptBSoft.
Energy Management
Compact Power Transducer
Type CPT-DIN "Basic version"
Model
Range code
System
Power supply
Outputs
Option
How to order
CPT-DIN AV5 3 H S1 BX
Type Selection
Power supply
L:
18 to 60VAC/DC
H:
90 to 260VAC/DC
(*) Pay attention: the 3-phase
measurement is carried out as
one current and one phase to
neutral voltage measurement.
Range codes
AV5:
400/(690)V
L-L
/5(6)AAC
VL-N: 185 V to 460 V
VL-L: 320 V to 800 V
AV6:
120/(208)V
L-L
/5(6)AAC
VL-N: 45 V to 145 V
VL-L: 78 V to 250 V
Phase current: 0.03A to 6A
Neutral current: 0.09 to 6A
Outputs
S1:
RS485 port
S2:
RS232 port
System
3 :
1, 2 or 3-phase,
unbalanced and
balanced load,
with or without
neutral
1 :
1-3-phase,
balanced load (*)
Rated inputs
Current
3 (current transformers)
Voltage
4
Accuracy (RS485/RS232)
with CT=1 and VT=1 AV5:
(@25C 5C, R.H.
60%) 1150W-VA-var,
FS:230VLN,
400VLL; AV6: 285W-VA-var,
FS: 57VLN, 100VLL
Current
0.25 to 6A: (0.5% FS +1DGT)
0.03A to 0.25A: (0.5% FS +7DGT)
Neutral current
0.25 to 6A: (1.5% FS +1DGT)
0.09A to 0.25A: (1.5% FS+7DGT)
Phase-phase voltage
(1.5% FS + 1DGT)
Phase-neutral voltage
(0.5% FS + 0.1DGT)
Active and Apparent power,
0.25 to 6A: (1%FS +1DGT);
0.03A to 0.25A: (1%FS+5DGT)
Reactive power
0.25 to 6A: (2% FS +1DGT);
0.03A to 0.25A: (2% FS +5DGT)
Active energy
Class 2 (I start up: 30mA)
Reactive energy
Class 3 (I start up: 30mA)
Frequency
0.1Hz (48 to 62Hz)
Additional errors
Humidity
0.3% FS, 60% to 90% RH
Temperature drift
200ppm/C
Sampling rate
1400 samples/s @ 50Hz
1700 samples/s @ 60Hz
Measurement refresh time
700ms
Measurement format
Instantaneous variables
4 DGT (Max indication: 9999)
Energies
9 DGT (Max indication:
999 999 99.9)
Hour counter
7 DGT (Max. indication:
9 999 9.99)
Input specifications
RS232 serial port on request
Alarms (only from serial communication port) V
LN
, An
Options
BX:
Basic features
How to order
CptBSoft: software to program the working parameters of
the transducer and to read the energy and the instanta-
neous variables. The kit includes the communication cable.
CptBSoft-kit
2
Specifications are subject to change without notice CPT-DINBDS190606
CPT-DIN
no parity, 1 stop bit
Baud-rate
9600 bit/s
Insulation
By means of optocuplers,
2kV
RMS
output to
measuring input.
4kV
RMS
output to power supply
RS232
Halfduplex communication
Type
Point to point connection
Connections
3-wire, max. distance 15m
Address
1 to 255 selectable via software
Protocol
MODBUS/JBUS (RTU)
Baud-rate
9600bits/s
other characteristics like
R422/RS485 port
RS422/RS485
Halfduplex communication
Type
Multidrop
bidirectional (static and
dynamic variables)
Connections
2 or 4 wires, max. distance
1200m, termination directly
on the instrument
Addresses
1 to 255 selectable via software
Protocol
MODBUS/JBUS (RTU)
Data (bidirectional)
Dynamic (reading only)
System, phase variables and
energies
Static (writing only)
All configuration parameters
Data format
1 start bit, 8 data bit,
Serial Port Specifications
Filter action
Measurements, alarms,
serial out. (fundamental var: V,
A, W and their derived ones).
Alarms
Programmable, for the V
LN
and
An (neutral current).
Note: the alarm is only a
status transmitted via
communication port.
Reset
Independent
alarm (V
LN
, An)
max: A dmd, W dmd
all energies (Wh, varh)
hour counter
System selection
3-ph. with or without N, unbal.
3-phase balanced "1CT + 1VT"
3-phase ARON, unbalanced
2-phase
Single phase
Transformer ratio
CT
1 to 999
VT/PT
1.0 to 99,9
Filter
Operating range
0 to 99.9% of the input
electrical scale
Filtering coefficient
1 to 16
Software functions
Input specifications (cont.)
Measurements
Current, voltage, power,
power factor, frequency,
energy, hour counter
Type
TRMS measurement
of distorted waves.
Coupling type
Direct
Crest factor
< 3, max 10A peak
Input impedance
400/690V
L-L
(
AV5)
1 M
5%
120/208V
L-L
(
AV6)
453 K
5%
Current
0.02
Frequency
48 to 62 Hz
Overload protection
(max values)
Continuos voltage/current
AV5: 460V
LN
, 800V
LL
/6A
AV6: 145V
LN
, 250V
LL
/6A
For 500ms: voltge/current
AV5: 800V
LN
, 1380V
LL
/36A
AV6: 240V
LN
, 416V
LL
/36A
Connections
RJ12 (3-wire) for special cable
Baud-rate
4800 bits/s
Data format
1 start bit, 8 data bit,
no parity, 1 stop bit
Insulation
By means of optocuplers,
2kV
RMS
output to
measuring input.
4kV
RMS
output to power supply
RS232 Configuration Bus
CptBSoft: parameter programming and reading data software
Working mode
Two different working
modes can be selected:
- management of a local
RS485 network;
- management of
communication from a single
instrument to PC (RS232);
Data access
By means of RS232 serial
port, RS485 serial port or
RS232 configuration port.
CptBSoft
Multi language software to
program the working
parameters of the transducer
and to read the energies and
the instantaneous variables.
The program runs under
Windows 95/98/98SE/2000/
NT/XP.
Specifications are subject to change without notice CPT-DINBDS190606
3
CPT-DIN
General Specifications
Front LED's
Power on
Green
Diagnostics
Green (TX data)
Red (RX data)
Operating
0 to +50C (32 to 122F)
temperature
(RH < 90% non condensing)
Storage
-10 to +60C (14 to 140F)
temperature
(RH < 90% non condensing)
Installation category
Cat. III (IEC 60664, EN60664)
Insulation (for 1 minute)
4kVAC
RMS
between mesuring
inputs and power supply.
2kVAC/DC between
mesuring inputs and
RS485/RS232/programming
port (RJ12)
4kVAC
RMS
between
power supply and
RS485/RS232/programming
port.
Dielectric strength
4kVAC
RMS
(for 1 min)
EMC
Emissions
EN61000-6-3, EN60688
residential environment,
commerce and light industry
Immunity
EN61000-6-2
industrial environment.
Pulse voltage (1.2/50s)
EN61000-4-5
Safety standards
IEC60664, EN60664
Measurement standards
IEC60688, EN60688
Approvals
CE, cURus
Connections 5(6) A
Screw-type
Max cable cross sect. area
2.5 mm
2
Housing
Dimensions (WxHxD)
45 x 83.5 x 98.5 mm
Material
ABS
self-extinguishing: UL 94 V-0
Mounting
DIN-rail
Protection degree
IP20
Weight
Approx. 200 g (pack. incl.)
Variables that can be retrasmitted 3-phase system 4-wire connection
Variables
Notes
V L1
V L2
V L3
V L12
V L23
V L31
A L1
A L2
A L3
A L1 dmd
A L2 dmd
A L3 dmd
dmd = demand (integration time
selectable from 1 to 30 minutes)
An
An alarm
An alarm: neutral current alarm
W L1
W L2
W L3
PF L1
PF L2
PF L3
var L1
var L2
var L3
VA L1
VA L2
VA L3
VA system
W system
var system
VA dmd
W dmd
Hz
dmd = demand (integration time
(system)
(system)
selectable from 1 to 30 minutes)
W dmd MAX
Maximum sys power demand
Wh
varh
V LL system
V
LN
alarm
PF system
V
LN
alarm: alarm status if V
LN
is not
within the two set limits.
A MAX
max. current among the three phases
A dmd max
max. dmd current among the three phases
h
working hour counter
Measurements available on the communication port
Auxiliary power supply
90 to 260VAC/DC
16 to 60VAC/DC
Power consumption
AC: 4.5 VA
DC: 4W
Power Supply Specifications
Used calculation formulas
4
Specifications are subject to change without notice CPT-DINBDS190606
CPT-DIN
Waveform of the signals that can be measured
Figure A
Sine wave, undistorted
Fundamental content
100%
Harmonic content
0%
A
rms
=
1.1107 | A |
Figure B
Sine wave, indented
Fundamental content
10...100%
Harmonic content
0...90%
Frequency spectrum: 3rd to 16th harmonic
Additional error: <1% FS
Figure C
Sine wave, distorted
Fundamental content
70...90%
Harmonic content
10...30%
Frequency spectrum: 3rd to 16th harmonic
Additional error: <0.5% FS
Accuracy
Wh, accuracy (RDG) depending on the current
Error
6A (Imax)
6A (Imax)
5A (Ib)
5A (Ib)
0.5A
(0.1Ib)
1A
(0.2Ib)
0.25A
(0.05Ib)
0.5A
(0.1Ib)
+2%
0%
+4%
-2%
Accuracy limits (Active energy)
5(6A) Start-up current: 30mA
-4%
varh, accuracy (RDG) depending on the current
Error
+3%
0%
+6%
-3%
Accuracy limits (Reactive energy)
5(6A) Start-up current: 30mA
-6%
PF=1
PF=L0.5
or C0.8
6A (Imax)
6A (Imax)
5A (Ib)
5A (Ib)
0.25A
(0.05Ib)
0.5A
(0.1Ib)
0.1A
(0.02Ib)
0.25A
(0.05Ib)
sin
=1
sin
=0.5
Phase variables
Instantaneous effective voltage
Instantaneous active power
Instantaneous power factor
Instantaneous effective current
Instantaneous apparent power
Instantaneous reactive power
System variables
Equivalent three-phase voltage
Three-phase reactive power
Neutral current
Three-phase active power
Three-phase apparent power
Three-phase power factor
(TPF)
Energy metering
Where:
i = considered phase (L1, L2 or L3)
P = active power
Q = reactive power
t
1
, t
2
=starting and ending time points
of consumption recording
n = time unit
t = time interval between two successive
power consumptions
n
1
, n
2
= starting and ending discrete time
points of consumption recording
An = A
L1
+A
L2
+A
L3
Specifications are subject to change without notice CPT-DINBDS190606
5
CPT-DIN
L1
L2
N
L3
L
N
-
+
F
A1
A2
7
11
8 10
23 25 27
L1 L2 L3
N
L1
L3
L2
L1
24
L2
26
L3
28
Wiring diagrams "system type selection: 3"
L1
L2
N
L
N
-
+
F
A1
A2
7
8 10
23 25
L1 L2
N
L1
L2
L1
24
L2
26
L1
N
L
N
-
+
F
A1
A2
7
8
23
L1
N
L1
L1
24
Direct connection
Direct connection
2-ph, 3-wire Fig. 3
L1
L2
L3
L
N
-
+
F
A1
A2
7
11
10
23 25 27
L1 L2 L3
L1
L3
L2
L1
24
L2
26
L3
28
ARON and 2VT/PT connection
2CT connection
3-ph, 4 wire, unbalanced load Fig. 4
1-ph, 2-wire Fig. 1
3-ph, 3-wire, unbalanced load Fig. 6
Power Supply
Power Supply
Power Supply
Power Supply
F= 630 mA T (18 to 60VAC/DC)
125 mA T (90 to 260VAC/DC)
L1
N
L
N
-
+
F
A1
A2
7
8
23
L1
N
L1
L1
24
1CT connection
1-ph, 2-wire Fig. 2
Power Supply
L1
L2
L3
L
N
-
+
F
A1
A2
7
11
8 10
N
L1
L3
L2
23 25 27
L1 L2 L3
L1
24
L2
26
L3
28
ARON connection
3-ph, 3-wire, unbalanced load Fig. 5
Power Supply