ChipFind - документация

Электронный компонент: DPC01DM48

Скачать:  PDF   ZIP
Mounting Output
Frequency
100 to 115 VAC
208 to 240 VAC
380 to 415 VAC
DIN-rail
2 x SPDT
50 - 60 Hz
DPC 01 D M23
DIN-rail
2 x SPDT
50 - 400 Hz
DPC 01 D M11 400HZ
DPC 01 D M23 400HZ
DPC 01 D M48 400HZ
Plug-in
2 x SPDT
50 - 60 Hz
PPC 01 D M23
PPC 01 D M48
Mounting Output
Frequency
440 to 480 VAC
380 to 480 VAC
600 to 690 VAC
DIN-rail
2 x SPDT
50 - 60 Hz
DPC 01 D M48
DPC 01 D M69
DIN-rail
2 x SPDT
50 - 400 Hz
DPC 01 D M49 400HZ
DPC 01 D M69 400HZ
Specifications are subject to change without notice (18.07.06)
1
Monitoring Relays
Product Description
Ordering key
Housing
Function
Type
Item number
Output
Power Supply
TRMS 3-phase over and under voltage,
phase sequence, phase loss and asymmetry
monitoring relay
Detect when all 3 phases are present and have the
correct sequence
Detect if all the 3-phase-phase or phase-neutral
voltages are within the set limits
Detect if asymmetry is below set value
Separately adjustable setpoints
Separately adjustable delay functions (0.1 to 30 s)
Output: 2 x 8 A relay SPDT NE
For mounting on DIN-rail in accordance with
DIN/EN 50 022 (DPC01) or plug-in module (PPC01)
45 mm Euronorm housing (DPC01) or 36 mm plug-in
module (PPC01)
LED indication for relays, alarm and power supply ON
Type Selection
True RMS 3-Phase, 3-Phase+N, Multifunction
Types DPC01, PPC01
Input Specifications (cont.)
Output
2 x SPDT relays N.E.
Rated insulation voltage
250 VAC
Contact ratings (AgSnO
2
)
Resistive loads
AC 1
8 A @ 250 VAC
DC 12
5 A @ 24 VDC
Small inductive loads AC 15
2.5 A @ 250 VAC
DC 13
2.5 A @ 24 VDC
Mechanical life
30 x 10
6
operations
Electrical life
10
5
operations
(at 8 A, 250 V, cos
= 1)
Operating frequency
7200 operations/h
Dielectric strength
Dielectric voltage
2 kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 s)
Output Specifications
DPC 01 D M48
3-phase or 3-phase+neutral
line voltage monitoring relay
for phase sequence, phase
loss, asymmetry, over and
under voltage (separately
adjustable set points) with
built-in time delay function.
Supply ranges from 100 to
690 VAC covered by three
multivoltage relays (ranges
over 415 VAC only on the
DIN-rail housing).
DPC01
PPC01
Note:
The input voltage must
not exceed the maximum rat-
ed voltage or drop below the
minimum rated voltage
reported above.
Input Specifications
Input
L1, L2, L3, N
DPC01:
Terminals L1, L2, L3, N
PPC01:
Terminals 5, 6, 7, 11
Measure on own supply
Note: Connect the neutral only
if it is intrinsically at the star
centre
Measuring ranges
M11
85 to 132
VAC
M23
177 to 275
VAC
M48
DPC01
323 to 550
VAC
DPC01 400HZ
323 to 475
VAC
PPC01
323 to 475
VAC
M49
DPC01
375 to 550
VAC
M69
DPC01
510 to 793
VAC
Ranges
Upper level
+2 to +22%
of the nominal voltage
Lower level
-22 to -2%
of the nominal voltage
Asymmetry
2 to 22%
of the nominal voltage
Tolerance
2 to 22%
of the nominal voltage
2
Specifications are subject to change without notice (18.07.06)
DPC01, PPC01
Mode of Operation
Asymmetry definition.
Asymmetry is an indicator of
the mains quality and it is
defined as the absolute val-
ue of the maximum devia-
tion among the mains volt-
ages, divided by the nominal
voltage of the 3-phase sys-
tem. The definition changes
according to the voltage ref-
erence:
1) in case of measuring
phase-phase voltages:
max |
V
PH-PH
|
V
NOM
2) in case of measuring
phase-neutral voltages:
max |
V
PH-N
|
V
NOM
Tolerance definition.
Tolerance is another indicator
of the mains quality and it is
definied as the absolute val-
ue of the maximum deviation
of the mains voltages from
the nominal voltage, divided
by the nominal voltage of the
3-phase system. The defini-
tion changes according to
the voltage reference:
1) in case of measuring
phase-phase voltages:
max |V
NOM
- V
PH-PH
|
V
NOM
2) in case of measuring
phase-neutral voltages:
max |V
NOM
- V
PH-N
|
V
NOM
Power supply
Overvoltage cat. III
Rated operational voltage
(IEC 60664, IEC 60038)
through terminals:
L1, L2, L3, N (DPC01)
5, 6, 7, 11 (PPC01)
M11 - Delta Voltage:
100 to 115VAC 15%; 45 to 65Hz
M23 - Delta Voltage:
208 to 240VAC 15%; 45 to 65Hz
DPC01 M48 - Delta Voltage:
380 to 480VAC 15%;45 to 65Hz
DPC01 M48 - Star Voltage:
220 to 277VAC 15%;45 to 65Hz
PPC01 M48 - Delta Voltage:
380 to 415VAC 15%;45 to 65Hz
PPC01 M48 - Star Voltage:
220 to 240VAC 15%;45 to 65Hz
M48 400HZ - Delta Voltage:
380 to 415VAC 15%;45 to 440Hz
M48 400 HZ- Star Voltage:
220 to 240VAC 15%;45 to 440Hz
M49 400HZ - Delta Voltage:
440 to 480VAC 15%;45 to 440Hz
M49 400 HZ- Star Voltage:
254 to 277VAC 15%;45 to 440Hz
M69 - Delta Voltage:
600 to 690VAC 15%;45 to 65Hz
M69 - Star Voltage:
347 to 400VAC 15%;45 to 65Hz
M69 400HZ- Delta Voltage:
600 to 690VAC 15%;45 to 440Hz
M69 400HZ- Star Voltage:
347 to 400VAC 15%;45 to 440Hz
Rated operational power
M11
8 VA @
115 VAC, 50 Hz
M23
9 VA @
230 VAC, 50 Hz
M48
13 VA @
400 VAC, 50 Hz
M69
21 VA @
600 VAC, 50 Hz
Supplied by L2 and L3 for
the DIN-rail versions and
by L1 and L2 for the Plug-in
versions
Supply Specifications
Reaction time
Incorrect phase sequence
or total phase loss
< 200 ms
Voltage level
(input signal variation from
-20% to +20% or from
+20% to -20% of set value)
Asymmetry level
Alarm ON delay:
< 200 ms (delay < 0.1 s)
Alarm OFF delay:
< 200 ms (delay < 0.1 s)
Indication for
Power supply ON
LED, green
Alarm ON
LED, red (flashing 2 Hz
during delay time)
Output relays ON
2 x LED, yellow
Environment
(EN 60529)
Degree of protection
IP 20
Pollution degree
3 (DPC01), 2 (PPC01)
Operating temperature
@ Max. voltage, 50 Hz
-20 to +60C, R.H. < 95%
@ Max. voltage, 50 Hz
-20 to +60C, R.H. < 95%
Storage temperature
-30 to +80C, R.H. < 95%
Housing
Dimensions
DPC01
45 x 80 x 99.5 mm
PPC01
36 x 80 x 94 mm
Weight
Approx. 220 g
Screw terminals
(DPC01)
Tightening torque
Max. 0.5 Nm
acc. to IEC 60947
Approvals
UL, CSA
GL (DPC01 only, except
400Hz, M11)
CE Marking
Yes
EMC
Electromagnetic Compatibility
Immunity
According to EN 61000-6-2
Emissions
According to EN 61000-6-3
General Specifications (cont.)
Power ON delay
1 s 0.5 s or 6 s 0.5 s
Accuracy
(15 min warm-up time)
Temperature drift
1000 ppm/C
Delay ON alarm
10% on set value 50 ms
Repeatability
0.5% on full-scale
General Specifications
x 100
x 100
x 100
x 100
L1
N
L3
L2
max V
D
PH-N
= V' -V'
L3-N
L2-N
|
|
|
|
N'
V
= V
L1-N
NOM
L2-N
L3-N
= V =V
L1
N
L3
L2
L1'
L3'
L2'
V'
L3-N
V'
L2-N
max V
D
PH-N
= 0
ASY = 0
|
|
max V
NOM
-V
= V
-V'
= V
-V'
= V
-V'
PH-N
NOM
L1-N
NOM
L2-N
NOM
L3-N
|
|
| |
| |
|
|
Y
Y
Y
Y
max V
NOM
PH-N
NOM
L3-N
-V
= V
-V'
|
| |
|
Y
Y
Y
L1
L2
L3
L1'
V
L3-L2
V'
L2-L1
max V
D
PH-PH
|
|
|
| =
V -V'
L3-L2
L2-L1
V
= V
L1-L3
D
NOM
L2-L1
L3-L2
= V = V
L1
L2
L3
L1'
V
L1-L2
V
L2-L1
V
L3-L2
V'
L1-L3
V'
L3-L2
V'
L2-L1
L2'
L3'
max V
-V
V
-V'
NOM
PH-PH
NOM
L2-L1
|
| = |
|
D
D
max V
D
PH-PN
= 0
ASY = 0
|
|
max V
NOM
PH-N
NOM
L1-L3
NOM
L2-L1
NOM
L3-L2
-V
= V
-V'
= V
-V'
= V
-V'
|
| |
| |
| |
|
D
D
D
D
Example: phase-neutral monitoring
Example: phase-phase monitoring
Specifications are subject to change without notice (18.07.06)
3
DPC01, PPC01
Function/Range/Level/Time Setting
Adjust the input range set-
ting the DIP-switches 3 and
4. Select the desired func-
tion setting the DIP-switches
5 and 6 as shown below. To
access the DIP-switches
open the plastic cover using
a
screwdriver as shown
below.
Centre knobs:
Setting of upper ( ) and low-
er ( ) level or setting of
asymmetry (ASY) and toler-
ance ( ) on relative scale.
Lower knobs:
Setting of delay on alarm
times (DELAY 1, DELAY 2)
on absolute scale:
0.1 to 30 s.
Power-ON delay
ON:
6 s 0.5 s
OFF:
1 s 0.5 s
Monitoring
ON:
Phase-Neutral voltages
OFF:
Phase-Phase voltages
Output
ON:
2 x SPDT relays
OFF:
1 x DPDT relay
Function
ON:
Asymmetry and tolerance monitoring
OFF:
Over and undervoltage monitoring
Measuring range
SW3
ON
ON
OFF
OFF
SW4
ON
OFF
ON
OFF
M11 Ph-Ph
100 VAC 100 VAC 115 VAC
115 VAC
Voltage
M23 Ph-Ph
208 VAC 220 VAC 230 VAC
240 VAC
Voltage
M48 Ph-Ph
380 VAC 400 VAC 415 VAC
480 VAC
Voltage
DPC01 only
M48 Ph-N
220 VAC 230 VAC 240 VAC
277 VAC
Voltage
DPC01 only
M49 Ph-Ph
440 VAC 440 VAC 480 VAC
480 VAC
Voltage
M49 Ph-N
254 VAC 254 VAC 277 VAC
277 VAC
Voltage
DPC01DM69 600 VAC 600 VAC 690 VAC
690 VAC
Ph-Ph Volt.
DPC01DM69 347 VAC 347 VAC 400 VAC
400 VAC
Ph-N Volt.
D
P
C
0
1
3
-
p
h
a
s
e
m
o
n
i
t
o
r
i
n
g
r
e
l
a
y
AL
1
3
0.1
30s
0.3
10
DELAY 2
1
3
0.1
30s
0.3
10
DELAY 1
2
22%
6
18
10
14
2
22%
6
18
10
14
/
D
P
C
0
1
3
-
p
h
a
s
e
m
o
n
i
t
o
r
i
n
g
r
e
l
a
y
1
3
0.1
30s
0.3
10
DELAY 2
1
3
0.1
30s
0.3
10
DELAY 1
2
22%
6
18
10
14
2
22%
6
18
10
14
/
AL
Mode of Operation (cont.)
Connected to the 3 phases
(and neutral) DPC01 and
PPC01 operate when all 3
phases are present at the
same time and the phase
sequence is correct. It can be
decided whether to monitor
upper and lower voltage level
of each phase or their asym-
metry and tolerance.
Voltage level monitoring:
if one or more phase-phase
or phase-neutral voltage
exceed the upper set level or
drop below the lower set lev-
el, the red LED starts flash-
ing 2 Hz and the respective
output relay releases after
the set time period.
Asymmetry and tolerance
monitoring:
if one or more phase-phase
or phase-neutral voltage
exceed the set levels the red
LED starts flashing 2 Hz and
the respective output relay
releases after the set time
period.
Note: For both functions, if
the phase sequence is
wrong or one phase is lost,
both output relays release
immediately. Only 200 ms
delay occurs. The failure is
indicated by the red LED
flashing 5 Hz during the
alarm condition.
Example 1
(Mains monitoring - over and
under phase-phase voltage)
The relay monitors over and
under voltage, phase loss
and correct phase sequence.
Example 2
(Motor monitoring - starting
and operating load -asym-
metry and tolerance of
phase-neutral voltage)
DPC01 and PPC01 ensure
correct starting and operat-
ing conditions. They monitor
the voltage level, phase
sequence (correct direction
of the motor rotation) and
asymmetry.
Frequent failures are fuse
blowing and incorrect volt-
age level. In case of fuse
blowing the motor regener-
ates a voltage in the inter-
rupted phase. The relay
detects the failure and reacts
due to excessive imbalance
among the phases.
DPC01
DPC01 400 HZ
P
P
C
0
1
3
-
p
h
a
s
e
m
o
n
i
t
o
r
i
n
g
r
e
l
a
y
AL
1
3
0.1
30s
0.3
10
DELAY 2
1
3
0.1
30s
0.3
10
DELAY 1
2
22%
6
18
10
14
2
22%
6
18
10
14
/
PPC01
4
Specifications are subject to change without notice (18.07.06)
Upper Level
Hysteresis
Hysteresis
Lower Level
Relay 1(Upper)
ON (15/16/18)
Relay 2 (Lower)
ON (25/26/28)
Red LED ON
L1 or
L1-L2
L2 or
L2-L3
1 or 6 s
1 or 6 s
1 or 6 s
L3 or
L1-L3
T
T
T
Red LED ON
Asymmetry (+)
Hysteresis
Balanced
Asymmetry (-)
Tolerance (+)
Hysteresis
Hysteresis
Tolerance (-)
L1 or
L1-L2
L2 or
L2-L3
L3 or
L1-L3
Relay 1 Asymmetry
(15/16/18) ON
1 or 6 s
T
T
T
1 or 6 s
1 or 6 s
T
T
Relay 2 Tolerance
(25/26/28) ON
L2-L1 or
V -V
L2-L1
L3-L2
L3-L2 or
V -V
L3-L2
L1-L3
L1-L3 or
V -V
L1-L3
L2-L1
Hysteresis
Nominal voltage
Operation Diagrams
DPC01, PPC01
Over and undervoltage monitoring (2 x SPDT relays)
Asymmetry and tolerance monitoring (2 x SPDT relays)
DELAY1
DELAY2
DELAY2
DELAY2
DELAY2
DELAY1
DELAY1
DELAY1
Specifications are subject to change without notice (18.07.06)
5
Operation Diagrams (cont.)
Phase sequence, total phase loss
DPC01, PPC01
Wiring Diagrams
DPC01
PPC01
Ex.1
Ex.2
Ex.1
Ex.2
6
Specifications are subject to change without notice (18.07.06)
DPC01, PPC01
45
8
0
8
3
.
5
99.5
6
3
28.5
36
8
0
94
28.5
6
3
90
Dimensions
DIN-rail
Plug-in