ChipFind - документация

Электронный компонент: B44066T0200E402

Скачать:  PDF   ZIP
Thyristor Module TSM-LC200

Series/Type: TSM
Ordering code: B44066T0200E402
Date: August
2006
Version:
4
Content of inside pages of data sheet. Data will be automatically entered into frontpage
headlines, headers and footers. Please fill in the table and then change the colour to "White".
This ensures that the table disappears for the customer pdf.
Identification/Classification 1:
(header 1)
Thyristor module for dynamic PFC
Identification/Classification 2:
(header 2)
Accessories for power factor correction
Ordering code:
B44066T0200E402
Series/Type:
Thyristor module TSM-LC200
Preliminary data (optional):
(if necessary)
Preliminary data
Department:
FK PC PM PFC
Date: August
2006
EPCOS AG 2006. Reproduction, publication and dissemination of this data sheet, enclosures hereto and the information
contained therein without EPCOS' prior express consent is prohibited.
Thyristor module for dynamic PFC
B44066T0200E402
Accessories for power factor correction
Thyristor module TSM-LC200
Preliminary data
Characteristics





Fast electronically controlled self observing thyristor
switch
For capacitive loads up to 200 kvar
Suitable for designing dynamic PFC-systems in 380 and
400 V grids
Micro-processor controlled alignment to tuned or
detuned capacitor branches (up to 14 %) for optimized
switching behaviour
No system perturbation due to switching operations
(transients)
Switching without delay
Maintenance-free
Long useful service life
No noise emission during switching operation
Compact module ready for connection

Features
Easy
installation
-
Mechanical assembly directly on a mounting plate
-
Self check after turn-on of main voltage
-
Optimized switching behaviour to the connected load
(tuned/detuned) via the internal processor
-
Storage of optimized parameters for optimum switching
behaviour
Mounting
position
-
Upright; minimum 150 mm space on top and below
Display and control via LED display
- Operation
- Faults
- Activation
Permanent
self-monitoring
- Temperature
- Voltage
- Operating
state
FK PC PM PFC
August 2006
Please read Cautions and warnings and
Page 2 of 6
Important notes at the end of this document.
Thyristor module for dynamic PFC
B44066T0200E402
Accessories for power factor correction
Thyristor module TSM-LC200
Preliminary data
Technical data
Dimensions
250 x 480 x 160 mm (w x h x d)
Weight 11.5
kg
Rated voltage
380 ... 400 V
Maximum voltage
- in conventional PFC-systems (without reactors)
- in detuned PFC-systems (7 % detuning)
- in detuned PFC-systems (14 % detuning)

440 V
440 V (no upwards tolerance permitted)
400 V
Auxiliary supply
230 V AC
Frequency 50/60
Hz
Switching capability
Max. 200 kvar at 400 V
Activation
10...24 V DC (approx. 20 mA) via terminal clamp,
internally electrically isolated
Switching time
Approx. 5 ms
Reset time
Depending on degree of detuning and dimension of
discharge resistor
Display
2 status LEDs per phase: operation/fault and triggering
signal
Power circuit
Direct connection 4 pole via busbar (cable lug max.
185 mm
2
, D = 12 mm), connection from the top
Power dissipation
P
D
(in W) = 2,0 x I (in A) ; at 400 V/200 kvar approx.
580 W thermal
Fuses (mandatory for protection of components)
3 x electronic fuse ,,superfast"
NH2 AC 690V, characteristic gRL
125 kvar: 315 A (e.g. SIBA Art.Nr. 20.212.20.315)
150 kvar: 350 A (e.g. SIBA Art.Nr. 20.212.20.350)
200 kvar: 450 A (e.g. SIBA Art.Nr. 20 212. 20.450)
Ambient operating temperature at nominal load
-10 C ... +55 C
FK PC PM PFC
August 2006
Please read Cautions and warnings and
Page 3 of 6
Important notes at the end of this document.
Thyristor module for dynamic PFC
B44066T0200E402
Accessories for power factor correction
Thyristor module TSM-LC200
Preliminary data
Connection diagram: three-phase load (standard)









FK PC PM PFC
August 2006
Please read Cautions and warnings and
Page 4 of 6
Important notes at the end of this document.
Thyristor module for dynamic PFC
B44066T0200E402
Accessories for power factor correction
Thyristor module TSM-LC200
Preliminary data
Cautions and Warnings

General
Thyristor modules TSM series may only be used for the purpose they have been designed for.
Thyristor modules TSM series may only be used in combination with appropriate pre-switched grid
separator device.
Thyristor modules have to be projected in such a way that in case of any failure no uncontrolled
high current and voltages may occur.
The devices in operation have to be protected against moisture and dust, sufficient cooling has to
be assured.

Attention
Due to the switching principle of the thyristor module the power capacitors are permanently loaded to
the peak value of the grid voltage (DC voltage) even when switched off. Therefore following rules
have to be obeyed in any case:
For standard PFC-systems (without reactors) power capacitors of 440 V nominal voltage have to
be used; for detuned systems PFC capacitors of 525 V nominal voltage have to be used.
Due to the high voltage (2 x peak value of nominal voltage) that occurs, the discharge resistors of
the power capacitors have to be replaced by special types.
In dynamic systems with TSM modules no fast discharge reactors may be used (reactor = DC-
wise short circuit).
For standard PFC-systems 2 current limiting reactors are mandatory per thyristor module.
Thyristor modules in general have to be protected by superfast electronic fuses. Principles for
dimensioning have to be considered. Fuses in the system have to be marked.
Due to the special switching, the PFC capacitors are fully loaded even when the particular step
has been switched off. Protection against contact has to be guaranteed. Warning signals in the
systems are required.
Even in switched off state no electrical isolation is achieved for electronic switches. Therefore
parts of the systems may not be touched after switching off the complete system before the
capacitors have been completely discharged.

FAILURE TO FOLLOW CAUTIONS MAY RESULT, WORST CASE, IN PREMATURE FAILURES OR
PHYSICAL INJURY.
U
Please read cautions information about PFC capacitors and cautions as well as installation and maintenance instructions in the actual
version of the Product Profile Power Factor Correction to ensure optimum performance and prevent products from failing, and in worst case,
bursting and fire, etc
.
The actual Product Profile is available at www.epcos.com/publications.
Information given in the PFC-product profile and values given in the data sheet reflect typical specifications. You are kindly requested to
approve our product specifications or request our approval for your specification before
ordering.


FK PC PM PFC
August 2006
Please read Cautions and warnings and
Page 5 of 6