60W DC-DC Converter P60A-Series

Offer single, dual and triple output
50 to 60 W Output power
2:1 Wide input voltage range
International safety standard approval
Six-Sided continuous shield
High efficiency up to 86%
Short circuit protection



Model selection guide
Input
Output 1
Output 2 (or Dual Output)
Typ
nominal
voltage
[V
DC
]
current
no load
[mA]
voltage

[V
DC
]
current

[A]
voltage

[V
DC
]
current

[A]
Efficiency
typ.

[%]
Output Power


[W]
Single output
P60A12S05P
9-18 20
5.0 12.0
79
60
P60A12S12P
9-18 20
12.0 5.0
82
60
P60A12S15P
9-18 20
15.0 4.0
82
60
P60A12S24P
9-18 20
24.0 2.5
84
60
P60A24S05P
18-36 15
5.0 12.0
80
60
P60A24S12P
18-36 15
12.0 5.0
84
60
P60A24S15P
18-36 15
15.0 4.0
84
60
P60A24S24P
18-36 15
24.0 2.5
85
60
P60A48S05P
36-72 10
5.0 12.0
83
60
P60A48S12P
36-72 10
12.0 5.0
85
60
P60A48S15P
36-72 10
15.0 4.0
85
60
P60A48S24P
36-72 10
24.0 2.5
86
60
Dual output
P60A12D05P
9-18 20
5.0 5.0
5.0
5.0
78
50
P60A12D12P
9-18 20
12.0 2.5
12.0
2.5
80
60
P60A12D15P
9-18 20
15.0 2.0
15.0
2.0
80
60
P60A12D512P
9-18 20
5.0 5.0
12.0
2.5
79
55
P60A24D05P
18-36 15
5.0 5.0
5.0
5.0
80
50
P60A24D12P
18-36 15
12.0 2.5
12.0
2.5
82
60
P60A24D15P
18-36 15
15.0 2.0
15.0
2.0
82
60
P60A24D512P
18-36 15
5.0 12.0
12.0
2.5
80
60
P60A48D05P
36-72 10
5.0 5.0
5.0
5.0
80
50
P60A48D12P
36-72 10
12.0 2.5
12.0
2.5
84
60
P60A48D15P
36-72 10
15.0 2.0
15.0
2.0
84
60
P60A48D512P
36-72 10
5.0 12.0
12.0
2.5
81
60
Triple output
P60A12T512P
9-18
20
5.0
5.0
12.0
1.25
78
55
P60A24T512P
18-36
15
5.0
5.0
12.0
1.25
79
55
P60A48T512P
36-72
10
5.0
5.0
12.0
1.25
80
55

Suffix "P" PCB mounting type, heat sink will be added on module.
Suffix "T" Chassis mounting type, (terminal block) heat sink or fan force cooling.
Indicate suffix when order!




Page 1 of 4
Deutschland: Schweiz:
Inselkammerstrae 10
Grndenstrae 82
D-82008 Unterhaching
CH-8247 Flurlingen
Tel.: 089 614 503-10
Tel.: 052 647 42 00
E-Mail: power@hy-line.de
E-Mail: power@hy-line.ch
60W DC-DC Converter P60A-Series

Specifications
Input
Voltage range
9-18 V
DC
18-36 V
DC
36-72 V
DC
Filter
Pi-type
Input reversed protection
Shunt diode built in,
external fuse recommended !
Output
Output Power
60 W max.
Voltage accuracy
(full load and nominal V
in
)
1%
Voltage adjustability
10%
Ripple and noise
(at 20 MHz BW)
1% of V
out
Short circuit
Coninuous
Line voltage regulation
(I
out
nom, V
in
min... V
in
max)
1%
Load voltage regulation
(I
out
min...I
out
nom)
Single output model: 2%
Dual output model: 2%
Triple output model: 5%
Transient recovery time @
25% load, step changed
500 s
Temperature coefficient
0.02% / C, max
Minimum load
Single: and Dual: 0%
+5V of triple output 0%
12V of triple output 20%






Derating



Page 2 of 4
General
Efficiency
See table
Switching frequency
80 kHz, typ.
Environmental
Operating temperature
ambient
-25C to +95C
(with derating, see diagram)
Operating temperature
case
+95 C, max.
Storage temperature range
-25 C to +100 C
Cooling
Free air convection
MTBF according to
MIL-HDBK-217F, GF40
122,500 hrs
Physical
Dimensions "P" model
3.5 x 5.5 x 1.4 inches
88.9 x 139.7 x 35.6 mm
Dimensions "T" model
3.5 x 5.5 x 1.29 inches
88.9 x 139.7 x 32.9 mm
Weight
"P" Model 690 g
"T" Model 570 g
Case material
metal
Isolation
Rated voltage
1500 V
DC
, min
Resistance
10
9
, min.
Remote control
Remote control on
Remote control off
Open or > + 5.5 V
DC
Short or 0V ... < + 1.8 V
DC
referenced to Input, pin 2
Shutdown idle current
10mA
Deutschland: Schweiz:
Inselkammerstrae 10
Grndenstrae 82
D-82008 Unterhaching
CH-8247 Flurlingen
Tel.: 089 614 503-10
Tel.: 052 647 42 00
E-Mail: power@hy-line.de
E-Mail: power@hy-line.ch
60W DC-DC Converter P60A-Series
Internal circuit schematic

Page 3 of 4
Deutschland: Schweiz:
Inselkammerstrae 10
Grndenstrae 82
D-82008 Unterhaching
CH-8247 Flurlingen
Tel.: 089 614 503-10
Tel.: 052 647 42 00
E-Mail: power@hy-line.de
E-Mail: power@hy-line.ch
60W DC-DC Converter P60A-Series


Pin connections
Trimming
Pin
Single
Dual
Triple
1
Omitted Omitted Omitted
2
- Input
- Input
- Input
3
- Input
- Input
- Input
4
+ Input
+ Input
+ Input
5
+ Input
+ Input
+ Input
6
Remote CTRL
Remote CTRL
Remote CTRL
7
NC NC NC
8
- Output
- Sense / Trim up
- Sense / Trim up
9
- Output
- Output
- Output
10
+ Output
+ Output
+ Output
11
+ Output
+ Sense/ trim down + Sense/ trim down
12
- Sense / Trim up
- Output 2
- Output 2
13
TRIM TRIM
Common Vo 2 & +Vo 3
14
+ Sense/ trim down
+ Output 2
+ Output 3

Dimensions
Deutschland: Schweiz:
Inselkammerstrae 10
Grndenstrae 82
D-82008 Unterhaching
CH-8247 Flurlingen
Tel.: 089 614 503-10
Tel.: 052 647 42 00
E-Mail: power@hy-line.de
E-Mail: power@hy-line.ch
Life Support Policy
: HY-LINE does not authorize the use of any of its products for use in life support devices or systems without the express
written approval of an officer of the Company. Life support systems are devices which support or sustain life, and whose failure to perform, when
properly used in accordance with instructions for use provided in the labeling, can be reasonably expected to result in significant injury to the
user. Rev: 11 / 2004 f
14
12
13
TRIM UP
TRIM DOWN
Page 4 of 4