ChipFind - документация

Электронный компонент: APR-B10

Скачать:  PDF   ZIP
Electrical data
Primary Nominal Current
Analogue Output Signal
Type
I
PN
(A.t.RMS)
V
OUT
(V)
10,25,50
0-5V or 0-10V
APR 50 B10
50,75,100
0-5V or 0-10V
APR 100 B10
100,150,200
0-5V or 0-10V
APR 200 B10
200,300,400
0-5V or 0-10V
APR 400 B10
R
L
Load resistance
10
k
V
C
Supply voltage
+24 5% V DC
V
d
R.m.s. voltage for AC isolation test,
50/60Hz, 1 mn
5
kV
Limitation of voltage output
18
V
Accuracy-Dynamic performance data
X
Accuracy @
I
PN
,
T
A
= 25C (without offset)
< 1
% of
I
PN

L
Linearity (0 ..
I
PN
)
< 0.5 % of
I
PN
V
OE
Electrical offset voltage,
T
A
= 25C
< 0.5 % of
I
PN
V
OT
Thermal drift of
V
OE
1
mV/K
TC

G
Thermal drift of the gain (% of reading)
0.1
%/K
t
r
Response time @ 90% of
I
P
< 1000
ms
f
Frequency bandwidth (-3 dB)
10 .. 6000
Hz
General data
T
A
Ambient operating temperature
-20 .. +60
C
T
S
Ambient storage temperature
-20 .. +85
C
m
Mass
90
g
Protection type
IP20
Reliable isolation according to EN50178, EN61010
300
V AC
Creepage distance
>
5.5
mm
EMC in accordance with EN50082-2
Plastic according to UL94V0, CTI 1
Notes :
Installation and maintenance should be done with power supply disconnected.
AC Current transducer APR-B10
Split core transducer for the electronic measurement distorted AC
waveforms current, with galvanic isolation between the primary (High
power) and the secondary circuits (Electronic circuit). Switch selectable
ranges and True RMS 0-5V and 0-10V switch selectable voltage output.
I
PN
= 10 .. 400 A
030708/0
Features
VFD and SCR waveforms current
measurement
True RMS output
Split core type
5V & 10V switch selectable voltage
output.
DIN mounting & Panel mounting
Eliminates insertion loss
Switch selectable ranges
Advantages
Large aperture for cable up to 18mm
High isolation between primary and
secondary circuits
Easy to mount
Applications
VFD Controlled Loads:
VFD output indicates how the motor
and attached load are operating.
SCR Controlled Loads:
Acurate measurement of phase angle
fired or burst fired (time proportioned)
SCRs. Current measurement gives
faster response than temperature
measurement.
Switching Power Supplies and
Electronic Ballasts:
True RMS sensing is the most
accurate way to measure power
supply or ballast input power.
LEM Components
www.lem.com
Preliminary
Dimensions AP(R)-B10
(unit : mm, 1mm = 0.0394 inch)
Mechanical characteristics
General tolerance
1 mm
Primary aperture
18.5 mm
Panel mounting
2 holes
4.0 mm
Distance between holes
40.0 mm
For panel mounting, replace M4 screws by new one (not supplied) with appropriate length to panels thickness.
Connections
Wires up to 2 mm
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
2 (out)1 (+)
3 (-)
O utput
R a n g e S w itc h
0-5, 10V Selec table
A P /A P R
C o n n e c to r
F ront
O utput S w itc h
G N D
O U T P U T
+2 4 V D C
R
L