Current Transducer HTA 100..1000-S
For the electronic measurement of DC, AC and pulsed currents,
with a galvanic isolation between the primary (high power) circuit
and the secondary (electronic) circuit.
Electrical data
Primary nominal
Primary current
Type
r.m.s. current
measuring range
I
PN
(A)
I
P
(A)
100
300
HTA 100-S
200
600
HTA 200-S
300
900
HTA 300-S
400
1000
HTA 400-S
500
1000
HTA 500-S
600
1000
HTA 600-S
1000
1000
HTA 1000-S
P
Overload capacity (Ampere Turns)
30000
A
V
OUT
Analogue output voltage @
I
PN
4
V
R
L
Load resistance
T
A
= 0 .. + 70C
> 1
k
T
A
= - 25 .. + 85C
> 3
k
V
C
Supply voltage ( 5 %)
15
V
I
C
Current consumption (max)
25
mA
V
b
Rms rated voltage
1)
500
V
V
d
Rms voltage for AC isolation test, 50 Hz, 1 mn
3
kV
R
is
Isolation resistance @ 500 V
DC
> 500
M
Accuracy - Dynamic performance data
X
Accuracy
2)
@
I
PN
,
T
A
= 25C, @ 15 V
1
%

L
Linearity
2)
0.5
%
Max
V
OE
Electrical offset voltage @
I
P
= 0,
T
A
= 25C
10
mV
V
OM
Residual offset voltage @
I
P
= 0
after an overload of 3 x
I
PN
10
mV
V
OT
Thermal drift of offset voltage
T
A
= - 25 .. + 85C
1
mV/K
TC

G
Thermal drift of gain
T
A
= - 25 .. + 85C
0.05
%/K
t
r
Response time @ 90 % of
I
P
< 3
s
di/dt
di/dt
accurately followed
> 50
A/s
f
Frequency bandwidth (- 3 dB)
3)
DC .. 50
kHz
General data
T
A
Ambient operating temperature
- 25 .. + 85
C
T
S
Ambient storage temperature
- 25 .. + 85
C
m
Mass
230
g
Standards Safety
EN50178 (1994)
EMC
EN50082-2 (1992)
EN50081-1 (1992)
Deviation in output when tested to EN 61000-4-6
< 10
% of
I
PN
Deviation in output when tested to EN 61000-4-4
< 10
% of
I
PN
Features
Open loop transducer using Hall
Effect
Panel mounting - Horizontal or
Vertical
Insulated plastic case to UL 94-V0.
Advantages
Very good linearity
Very good accuracy
Low temperature drift
Wide frequency bandwidth
Very low insertion losses
High immunity to external
interference
Current overload capability
Low power consumption
Wide dynamic range, 100 to 1000 A
in one package.
Applications
AC variable speed drives and servo
motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptable Power Supplies
(UPS)
Switched Mode Power Supplies
(SMPS)
Power supplies for welding
applications.
I
PN
= 100 A
001107/1
Notes :
1)
Overvoltage
Category III, Pollution Degree 2
2)
Excludes the electrical offset
3)
Refer to derating curves in the technical file to avoid excessive core
heating at high frequency
LEM have a policy of continual product improvement and the company reserves the right to revise the above specification without prior notice.
Secondary terminals
Terminal 1
: supply voltage + 15 V
Terminal 2
: supply voltage - 15 V
Terminal 3
: output
Terminal 4
: 0V
Remarks
V
OUT
is positive when
I
P
flows in the direction of the arrow.
Temperature of the primary conductor should not exceed
90C.
This is a standard model. For different versions (supply
voltages, secondary connections, unidirectional measure-
ments, operating temperatures, etc.) please contact us.
Mechanical characteristics
General tolerance
0.5 mm
Primary through-hole
32 mm
Connection of secondary
Molex 5045-04-A
Dimensions HTA 100..1000-S
(in mm)
Bottom view
Front view
Left view