ChipFind - документация

Электронный компонент: LT10000-S

Скачать:  PDF   ZIP
Current Transducer LT 10000-S
For the electronic measurement of currents : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
Electrical data
I
PN
Primary nominal r.m.s. current
10000
A
I
P
Primary current, measuring range (1 s
/
mn)
0 .. 15000
A
R
M
Measuring resistance
R
M min
R
M max
with 48 V
@ 10000 A
max
0
8
@ 12000 A
max
0
1
with 60 V
@ 10000 A
max
0
20
@ 15000 A
max
0
1.5
I
SN
Secondary nominal r.m.s. current
1
A
K
N
Conversion ratio
1 : 10000
V
C
Supply voltage ( 5 %)
48 .. 60
V
I
C
Current consumption
40
(@ 60 V) +
I
S
mA
V
d
R.m.s. voltage for AC isolation test, 50 Hz, 1 mn
10
1)
kV
1
2)
kV
Accuracy - Dynamic performance data
X
G
Overall accuracy @ I
PN
, T
A
= 25C
0.3
%
L
Linearity
< 0.1
%
Typ
Max
I
O
Offset current @ I
P
= 0, T
A
= 25C
1.5
mA
I
OT
Thermal drift of I
O
- 25C .. + 70C
0.6 0.8
mA
t
r
Response time
3)
@ 90 % of I
P max
< 1
s
di/dt
di/dt accurately followed
> 50
A/s
f
Frequency bandwidth (-
1
dB)
DC .. 100
kHz
General data
T
A
Ambient operating temperature
- 25 .. + 70
C
T
S
Ambient storage temperature
- 40 .. + 85
C
R
S
Secondary coil resistance @ T
A
= 70C
35
m
Mass
17
kg
Standards
4)
EN 50178
Notes :
1)
Between primary and secondary + shield
2)
Between secondary and shield
3)
With a di/dt of 100 A/s
4)
A list of corresponding tests is available
Features
Closed loop (compensated) current
transducer using the Hall effect
Insulated case.
Advantages
Excellent accuracy
Very good linearity
Low temperature drift
Optimized response time
Wide frequency bandwidth
No insertion losses
High immunity to external
interference
Current overload capability.
Applications
AC variable speed drives and servo
motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies
(UPS)
Switched Mode Power Supplies
(SMPS)
Power supplies for welding
applications.
I
PN
= 10000
A
980708/6
LEM Components
w w w .lem.com
Secondary terminals
Terminal +
: supply voltage + 48 .. 60 V
Terminal M : measure
Terminal 0 V : 0 V
Terminal
-
: supply voltage - 48 .. 60 V
Terminal E : shield
Remarks
I
S
is positive when I
P
flows in the direction of the arrow.
Temperature of the primary conductor should not exceed
100C.
Dynamic performances (di/dt and response time) are best
with a primary bar in the center of the through-hole.
This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...),
please contact us.
Mechanical characteristics
General tolerance
1 mm
Fastening
4 holes
11 mm
Primary through-hole
200 mm
Connection of secondary
M5 threaded studs
Fastening torque
2.2 Nm or 1.62 Lb - Ft
Dimensions LT 10000-S
(in mm. 1 mm = 0.0394 inch)
Left view
Front view
Connection
or
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.