ChipFind - документация

Электронный компонент: LT1005-S

Скачать:  PDF   ZIP
Current Transducer LT 1005-S
For the electronic measurement of currents : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
Electrical data
I
PN
Primary nominal r.m.s. current
1000
A
I
P
Primary current, measuring range
0 .. 2000
A
R
M
Measuring resistance @
T
A
= 70C
T
A
= 85C
R
M min
R
M max
R
M min
R
M max
with 15 V
@ 1000 A
max
0
22.5
0
18.5
@ 1200 A
max
0
11
0
8
with 24 V
@ 1000 A
max
0
65
0
62
@ 2000 A
max
0
10
0
7
I
SN
Secondary nominal r.m.s. current
200
mA
K
N
Conversion ratio
1 : 5000
V
C
Supply voltage ( 5 %)
15 .. 24
V
I
C
Current consumption
30
(@ 24 V) +
I
S
mA
V
d
R.m.s. voltage for AC isolation test, 50 Hz, 1 mn
6
kV
V
b
R.m.s. rated voltage
1)
, safe separation
1750
V
basic isolation
3500
V
Accuracy - Dynamic performance data
X
G
Overall accuracy @ I
PN
, T
A
= 25C
0.4
%
L
Linearity
< 0.1
%
Typ
Max
I
O
Offset current @ I
P
= 0, T
A
= 25C
0.4
mA
I
OT
Thermal drift of I
O
- 10C .. + 85C
0.3 0.5
mA
t
r
Response time
2)
@ 90 % of I
P max
< 1
s
di/dt
di/dt accurately followed
> 50
A/s
f
Frequency bandwidth (- 1 dB)
DC .. 150
kHz
General data
T
A
Ambient operating temperature
- 10 .. + 85
C
T
S
Ambient storage temperature
- 25 .. + 100
C
R
S
Secondary coil resistance @
T
A
= 70C
43
T
A
= 85C
46
m
Mass
320
g
Standards
3)
EN 50178
Notes :
1)
Pollution class 2. With a non insulated primary bar which fills the
through-hole
2)
With a di/dt of 100 A/s
3)
A list of corresponding tests is available
Features
Closed loop (compensated) current
transducer using the Hall effect
Insulated plastic case recognized
according to UL 94-V0.
Advantages
Excellent accuracy
Very good linearity
Low temperature drift
Optimized response time
Wide frequency bandwidth
No insertion losses
High immunity to external
interference
Current overload capability.
Applications
AC variable speed drives and servo
motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies
(UPS)
Switched Mode Power Supplies
(SMPS)
Power supplies for welding
applications.
I
PN
= 1000
A
980716/4
LEM Components
w w w .lem.com
Secondary terminals
Terminal + : supply voltage + 15 .. 24 V
Terminal M : measure
Terminal - : supply voltage - 15 .. 24 V
Connection
Mechanical characteristics
General tolerance
0.5 mm
Fastening
4 holes
6.5 mm
Primary through-hole
40.5 x 40.5 mm
Connection of secondary
Faston 6.3 x 0.8 mm
Dimensions LT 1005-S
(in mm. 1 mm = 0.0394 inch)
Front view
Top view
Left view
Remarks
I
S
is positive when I
P
flows in the direction of the arrow.
Temperature of the primary conductor should not exceed
100C.
Dynamic performances (di/dt and response time) are best
with a single bar completely filling the primary hole.
This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...),
please contact us.
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.