SPECIFICATIONS
Voltage Rating: 600 volts AC
Interrupting Rating: 200,000 Amperes
Cable Size Range: 4/0 750MCM Copper or Aluminum
Minimum Operating Temperature: 80C
Cable limiters are fusible devices that provide very fast
short-circuit protection, primarily to faulted cables, but also
to other conductors such as busway. Cable limiters do not
have an ampere rating, and cannot be used to provide over-
load protection. Cable limiters are selected by cable size;
for example, a 500 kcmil cable requires a 500 kcmil cable
limiter. Their main use is to isolate faulted cables in circuits
containing three or more parallel conductors per phase.
They may be installed on the line side of the main service
to provide short-circuit protection to the service conductors.
This is especially important when service conductors are
tapped from large low-voltage networks or from large low
impedance transformers.
Cable limiters have terminals which permit them to be
installed in a variety of equipment. The most common
configuration is the offset blade on one end and the crimp
terminal on the other end. This permits the limiter to replace
a cable terminal (lug).
APPLICATIONS
Service entrance conductors
Between transformer or network bus and busway
terminal boxes
Large feeders with three or more conductors per phase
FEATURES
s
Current-limiting characteristics provide protection to
conductor insulation and reduce damage when faults occur.
s
Properly applied cable limiters may permit the use of
equipment with reduced withstand ratings
s
Wide variety of terminations and cable ratings permit use
in almost every situation.
Cable Limiters
600 Volts AC
ORDERING INFORMATION
LFCL
1
-
C
-
500
-
DESCRIPTION
CATALOG NUMBER
Type Termination Cable Size
Cable Type
COPPER
ALUMINUM
4/0
LFCL4/0C1
LFCL4/0A1
250MCM
LFCL250C1 LFCL250A1
1
350MCM
LFCL350C1 LFCL350A1
Cable to
500MCM
LFCL500C1 LFCL500A1
Cable
750MCM
LFCL750C1 LFCL750A1
4/0
LFCL4/0C3
LFCL4/0A3
250MCM
LFCL250C3 LFCL250A3
3
350MCM
LFCL350C3 LFCL350A3
Cable to
500MCM
LFCL500C3 LFCL500A3
Offset Bus
750MCM
LFCL750C3 LFCL750A3
4/0
LFCL4/0C5
250MCM
LFCL250C5
5
Straight Bus
350MCM
LFCL350C5
to
500MCM
LFCL500C5
Offset Bus
750MCM
LFCL750C5
4/0
LFCL4/0C6
LFCL4/0A6
250MCM
LFCL250C6 LFCL250A6
6
350MCM
LFCL350C6 LFCL350A6
Mole to
500MCM
LFCL500C6 LFCL500A6
Cable
750MCM
LFCL750C6 LFCL750A6
4/0
LFCL4/0C8
250MCM
LFCL250C8
8
350MCM
LFCL350C8
Mole to
500MCM
LFCL500C8
Offset Bus
750MCM
LFCL750C8
Conductor Siz
e
Littelfuse
Cab
le Limiter
T
e
r
minal Mater
ial
(Alumin
um or Copper)
T
ype of
T
e
r
mination
Contact factory for shrink tubing availability.