ChipFind - документация

Электронный компонент: 0063ADT6

Скачать:  PDF   ZIP
ADT Series
ADT Series
CORCOM Product Guide
10
Catalog 1654001
Dimensions are in inches and
Dimensions are shown for
USA Cust. Svc.: 1-800-468-2023
www.cor.com
Revised 03-04
millimeters unless otherwise
reference purposes only.
CORCOM Prods: 1-847-680-7400
www.tycoelectronics.com
specified. Values in italics
Specifications subject
1-508-992-4495
are metric equivalents.
to change.
Germany: 49-89-6089-0
High Performance Filters for High Current Three Phase Applications
Designed with very high insertion loss for Delta
applications, these three phase filters work well in industrial
applications to bring high current motor drives into
compliance with the European EMC Directives.
The series offers filters between 63 and 200 amps at 480
VAC phase-to-phase. It is available with common or
differential mode (S models) coils for the correct protection
to fit the application.
Typical insertion loss in dB:
Line-to-ground in 50 ohm circuit:
Current
Frequency-MHz
Rating
.01
.1
1
10
30
100
300
00
63ADT6
45
85
95
100
100
100
100
0
100ADT6
45
85
90
100
100
100
100
0
160ADT6
45
80
90
100
100
100
100
0
200ADT6
45
77
88
100
100
100
100
0
63ADT6S
28
45
90
90
90
90
90
100ADT6S
38
60
95
100
100
100
100
160ADT6S
37
58
85
100
100
100
100
200ADT6S
35
54
80
100
100
100
100
Line-to-line in 50 ohm circuit:
Current
Frequency-MHz
Rating
.01
.1
1
10
30
100
300
00
63ADT6
35
100
100
100
100
100
100
0
100ADT6
43
100
100
100
100
100
100
0
160ADT6
44
100
100
100
100
100
100
0
200ADT6
43
100
100
100
100
100
100
0
63ADT6S
35
100
100
100
100
100
100
100ADT6S
43
100
100
100
100
100
100
160ADT6S
44
100
100
100
100
100
100
200ADT6S
43
100
100
100
100
100
100
UL Recognized
Specifications
Maximum leakage current, each line-to-ground
ADT6/ADT6S
0.76A/2.7A @ 230V 50 Hz
63ADT6S
1.5A @ 230V 50 Hz
Hipot rating (one minute):
line-to-ground
2250 VDC
line-to-line
2160 VDC
Operating frequency:
50/60 Hz
Rated voltage:
phase-to-phase:
480 VAC
phase-to-ground:
277 VAC
ADT6/ADT6S
Electrical Schematics
ADT6
LINE
LOAD
ADT6S
LINE
LOAD
ADT Series
CORCOM Product Guide
11
Catalog 1654001
Dimensions are in inches and
Dimensions are shown for
USA Cust. Svc.: 1-800-468-2023
www.cor.com
Revised 03-04
millimeters unless otherwise
reference purposes only.
CORCOM Prods: 1-847-680-7400
www.tycoelectronics.com
specified. Values in italics
Specifications subject
1-508-992-4495
are metric equivalents.
to change.
Germany: 49-89-6089-0
RFI Power Line Filters
High Performance Filters for High Current Three Phase Applications
(Continued)
Case Style
A
D B
C
E
1.00
25.4
.75
19.0
2.00
50.8
1.00
25.4
2.00
50.8
1.18 x .56
Cutout
.69
17.5
3/8 - 16 Steel
Case Dimensions
Part No.
A
B
C
D
E
.030
(max)
(max)
(max)
(max)
.76
63ADT6
14.00
10.00
3.50
8.50
10.00
355.6
254.0
89.0
216.0
254.0
63ADT6S
19.00
10.00
4.50
8.50
15.00
482.6
254.0
114.3
216.0
381.0
100ADT6
19.00
10.00
4.50
8.50
15.00
482.6
254.0
114.3
216.0
381.0
100ADT6S
19.00
11.00
4.50
8.50
15.00
482.6
279.4
114.3
216.0
381.0
160/200ADT6
19.00
10.00
4.50
8.50
15.00
482.6
254.0
114.3
216.0
381.0
160/200ADT6S 22.00
13.00
4.50
11.50
18.00
558.8
330.2
114.3
292.2
457.2
Part Numbers
0
63ADT6
0
63ADT6S
100ADT6
100ADT6S
160ADT6
160ADT6S
200ADT6
200ADT6S
Terminals:
63ADT6, 63ADT6S, 100ADT6S:
3/8-16 (6)
Torque (Max.): 70 in.lb.
100ADT6, 160ADT6, 160ADT6S, 200ADT6, 200ADT6S: 7/16-20 (6)
Torque (Max.): 125 in.lb.