1
General-purpose Relay
LY
A Miniature Power Relay
Equipped with arc barrier.
Withstand voltage: 2,000 V.
R
C+Y
LR

Ordering Information
Open Relays
Type
Contact form
Plug-in/solder
terminals
Plug-in/solder
terminals with
indicator
PCB terminals
Upper-mounting
Plug-in/solder
terminals
Standard
SPDT
LY1
LY1N
LY1-0
LY1F
DPDT
LY2
LY2N
LY2-0
LY2F
DPDT (bifurcated)
LY2Z
LY2ZN
LY2Z-0
LY2ZF
3PDT
LY3
LY3N
LY3-0
LY3F
4PDT
LY4
LY4N
LY4-0
LY4F
4PDT (bifurcated)
LY4Z
LY4ZN
LY4Z-0
LY4ZF
With built-in diode
SPDT
LY1-D
LY1N-D2
(DC only)
DPDT
LY1-D
LY2N-D2
DPDT (bifurcated)
LY2Z-D
LY2ZN-D2
3PDT
LY3-D
4PDT
LY4-D
LY4N-D2
4PDT (bifurcated)
LY4Z-D
With built-in CR
SPDT
(AC only)
DPDT
LY2-CR
LY2N-CR
DPDT (bifurcated)
LY2Z-CR
LY2ZN-CR
With built-in varister
3PDT
(AC only)
4PDT
LY4-Y-V
LY4N-V
4PDT (bifurcated)
Back
LY
LY
2
Type
Contact form
Plug-in/solder
terminals
Plug-in/solder
terminals with
indicator
PCB terminals
Upper-mounting
Plug-in/solder
terminals
High-humidity
SPDT
LY1-TU
DPDT
LY2-TU
DPDT (bifurcated)
LY2Z-TU
3PDT
LY3-TU
4PDT
LY4-TU
4PDT (bifurcated)
LY4Z-TU
With test button
SPDT
DPDT
LY2I2
LY2I2N
DPDT (bifurcated)
LY2ZI2
LY2ZI2N
3PDT
LY3I2
4PDT
LY4I2
LY4I2N
4PDT (bifurcated)
LY4ZI2
LY4ZI2
Rated coil voltage
Note:
1. When ordering, add the rated coil voltage to the model number. Rated coil voltages are given in the coil ratings table.
Example: LY2, 6 VAC
2. Relays with #187 quick connect terminals are also available with SPDT and DPDT contact. Ask you OMRON representative for
details.
3. SEV models are standard relays only. Relays with built-in varisters have not met overseas standards.
4. VDE- or LR- qualifying relays must be specified when ordering.
Accessories (Order Separately)
Sockets
Poles
Front-connecting socket
Back-connecting socket
DIN rail/screw terminals
Solder terminals
Wrapping terminals
PCB terminals
1 or 2
PTF08A-E, PTF08A
PT08
PT08QN
PT08-0
3
PTF11A
PT11
PT11QN
PT11-0
4
PTF14A-E, PTF14A
PT14
PT14QN
PT14-0
Note:
1. For PTF08-E and PTF14A-E, see "Track Mounted Socket".
2. PTF
j
AY (-E) sockets have met UL and CSA standards: UL 508/CSA C22.2.
Mounting Plates for Sockets
Socket model
For 1 socket
For 10 sockets
For 12 sockets
For 18 sockets
PT08
PT08QN
PYP-1
PYP-18
PT11
PT11QN
PTP-1-3
PTP-12
PT14
PT14QN
PTP-1
PTP-10
LY
LY
3
SocketHold-down Clip Pairings
Relay type
Poles
Front-connecting sockets
Back-connecting sockets
Socket model
Clip model
Socket model
Clip model
Standard, bifurcated contacts
1, 2
PTF08A-E, PTF08A
PYC-A1
PT08(QN), PT08-0
PYC-P
operation indicator, built-in
3
PTF11A
PT11(QN), PT11-0
diode, or high-humidity
4
PTF14A-E, PTF14A
PT14(QN), PT14-0
LY2N-D4
2
PTF08A-E, PTF08A
Y92H-3
PT08(QN), PT08-0
PYC-1
Test button
1, 2
PTF08A-E, PTF08A
PYC-A1
PT08(QN), PT08-0
PYC-P2
3
PTF11A
PT11(QN), PT11-0
PYC-P
(PYC-P2 for LY31)
4
PTF14A-E, PTF14A
PT14(QN), PT14-0
PYC-P2
CR circuit
1, 2
PTF08A-E, PTF08A
Y92H-3
PT08(QN), PT08-0
PYC-1
Built-in varister
4
PTF14A-E, PTF14A
PYC-A1
PT14(QN), PT14-0
PYC-P
Specifications
Coil Ratings
Single- and Double-pole Relays
Rated voltage
Rated current
Coil resis-
tance
Inductance
(reference value)
Must
operate
voltage
Must
release
voltage
Max.
voltage
Power
consum.
(approx.)
50 Hz
60 Hz
Arm.
OFF
Arm. ON
of rated voltage
AC
6 V
214.1 mA
183 mA
12.2
0.04 H
0.08 H
80%
30%
110%
1.0 to 1.2
12 V
106.5 mA
91 mA
46
0.17 H
0.33 H
max.
min.
VA
24 V
53.8 mA
46 mA
180
0.69 H
1.30 H
(60 Hz)
50 V
25.7 mA
22 mA
788
3.22 H
5.66 H
100/110 V
11.7/12.9 mA
10/11 mA
3,750
14.54 H
24.6 H
0.9 to 1 VA
110/120 V
9.9/10.8 mA
8.4/9.2 mA
4,430
19.20 H
32.1 H
(60 Hz)
200/220 V
6.2/6.8 mA
5.3/5.8 mA
12,950
54.75 H
94.07 H
220/240 V
4.8/5.3 mA
4.2/4.6 mA
18,790
83.50 H
136.40 H
DC
6 V
150 mA
40
0.16 H
0.33 H
10%
min.
0.9 W
12 V
75 mA
160
0.73 H
1.37 H
24 V
36.9 mA
650
3.20 H
5.72 H
48 V
18.5 mA
2,600
10.6 H
21.0 H
100/110 V
9.1/10 mA
11,000
45.6 H
86.2 H
Note:
See notes on the bottom of next page.
LY
LY
4
Three-pole Relays
Rated voltage
Rated current
Coil resis-
tance
Inductance
(reference value)
Must
operate
voltage
Must
release
voltage
Max.
voltage
Power
consum.
(approx)
50 Hz
60 Hz
Arm.
OFF
Arm. ON
of rated voltage
AC
6 V
310 mA
270 mA
6.7
0.03 H
0.05 H
80%
30%
110%
1.6 to 2.0
12 V
159 mA
134 mA
24
0.12 H
0.21 H
max.
min.
VA
24 V
80 mA
67 mA
100
0.44 H
0.79 H
(60 Hz)
50 V
38 mA
33 mA
410
2.24 H
3.87 H
100/110 V
14.1/16 mA
12.4/13.7 mA
2,300
10.5 H
18.5 H
200/220 V
9.0/10.0 mA
7.7/8.5 mA
8,650
34.8 H
59.5 H
DC
6 V
234 mA
25.7
0.11 H
0.21 H
10%
1.4 W
12 V
112 mA
107
0.45 H
0.98 H
min.
24 V
58.6 mA
410
1.89 H
3.87 H
48 V
28.2 mA
1,700
8.53 H
13.9 H
100/110 V
12.7/13 mA
8,500
29.6 H
54.3 H
Note:
See notes under next table.
Four-pole Relays
Rated voltage
Rated current
Coil resis-
tance
Inductance
(reference value)
Must
operate
voltage
Must
release
voltage
Max.
voltage
Power
consum.
(approx)
50 Hz
60 Hz
Arm.
OFF
Arm. ON
of rated voltage
AC
6 V
386 mA
330 mA
5
0.02 H
0.04 H
80%
30%
110%
1.95 to 2.5
12 V
199 mA
170 mA
20
0.10 H
0.17 H
max.
min.
VA
24 V
93.6 mA
80 mA
78
0.38 H
0.67 H
(60 Hz)
50 V
46.8 mA
40 mA
350
1.74 H
2.88 H
100/110 V
22.5/25.5 mA
19/21.8 mA
1,600
10.5 H
17.3 H
200/220 V
11.5/13.1 mA
9.8/11.2 mA
6,700
33.1 H
57.9 H
DC
6 V
240 mA
25
0.09 H
0.21 H
10%
1.5 W
12 V
120 mA
100
0.39 H
0.84 H
min.
24 V
69 mA
350
1.41 H
2.91 H
48 V
30 mA
1,600
6.39 H
13.6 H
100/110 V
15/15.9 mA
6,900
32 H
63.7 H
Note:
1. The rated current and coil resistance are measured at a coil temperature of 23
C with tolerances of +15%/20% for rated currents
and
15% for DC coil resistance.
2. Performance characteristic data are measured at a coil temperatures of 23
C.
3. AC coil resistance and impedance are provided as reference values (at 60 Hz).
4. Power consumption drop was measured for the above data. When driving transistors, check leakage current and connect a bleeder
resistor if required.
LY
LY
5
Contact Ratings
Single contact
Relay
1-pole
2, 3 or 4-pole
Bifurcated contacts
Load
Resistive load
(cos
= 1)
Inductive load
(cos
=0.4,
L/R=7 ms)
Resistive load
(cos
= 1)
Inductive load
(cos
=0.4,
L/R=7 ms)
Resistive load
(cos
= 1)
Inductive load
(cos
=0.4,
L/R=7 ms)
Rated load
100 VAC 15 A
24 VDC 15 A
110 VAC 10 A
24 VDC 7 A
110 VAC 10 A
24 VDC 10 A
110 VAC 7.5 A
24 VDC 5 A
110 VAC 5A
24 VDC 5 A
110 VAC 4 A
24 VDC 4A
Rated carry
current
15 A
10 A
7 A
Max.
switching
voltage
250 VAC
125 VDC
250 VAC
125 VDC
250 VAC
125 VDC
Max.
switching
current
15 A
10 A
7 A
Max.
switching
capacity
1,700 VA
360 W
1,100 VA
170 W
1,100 VA
240 W
825 VA
120 W
550 VA
120 W
440 VA
100 W
Min.
permissible
load*
100 mA, 5 VDC
100 mA, 5 VDC
10 mA, 5 VDC
*Note: P level:
60
= 0.1 x 10
-6
/operation, reference value
Characteristics
Item
All but relays with bifurcated contacts
Relays with bifurcated contacts
Contact resistance
50 m
max.
Operate time
25 ms max.
Release time
25 ms max.
Max. operating frequency
Mechanical: 18,000 operations/hr
Electrical:
1,800 operations/hr (under rated load)
Insulation resistance
100 M
min. (at 500 VDC)
Dielectric withstand voltage
1,000 VAC, 50/60 Hz for 1 min between contacts of same polarity
2,000 VAC, 50/60 Hz for 1 min between contacts of different polarity
Vibration resistance
Destruction: 10 to 55 Hz, 1.0-mm double amplitude
Malfunction: 10 to 55 Hz, 1.0-mm double amplitude
Shock resistance
Destruction: 1,000 m/s
2
(approx. 100G)
Malfunction: 200 m/s
2
(approx. 20G)
Life expectancy
Mechanical: AC: 50,000,000 operations min. (at 18,000 operations/hr)
DC: 1,00,000,000 operations min. (at 18,000 operations/hr)
Electrical:
Single-, three-, and four-pole: 200,000 operations min. (at 1,800 operations/hr
under rated load)
Double-pole: 500,000 operations min. (at 1,800 operations/hr under rated load)
Ambient operating temperature*
Single- and double-pole standard, bifcurcated-contact, test-button, and high-humidity relays:
25
C to 55
C (with no icing) (25
C to 70
C if carry current is 4 A or less)
All other relays: 25
C to 40
C (with no icing) (25
C to 55
C if carry current is 4 A or less)
Ambient operating humidity
35% to 85% (35% to 90% for high-humidity relays)
Weight
Single- and double-pole: approx. 40 g, three-pole: approx. 50 g, four-pole: approx. 70 g
Note:
1. The values given above are initial values.
*2. The upper limit of 40