ChipFind - документация

Электронный компонент: TCL024-124C

Скачать:  PDF   ZIP
http://www.tracopower.com
Page 1 of 5
Industrial Power Supplies
TCL Series, 24120 Watt
Features
For Industrial, Office and Residential
Application
Ultracompact Plastic Housing
Connection by Cage Clamps Terminals
or plugable Screw Terminals
Reliable snap-on Mounting on DIN-Rails
Adaptor for Wall Mounting
Universal Input 85-264 VAC, 50/60 Hz
Models with 5, 12, 24 and 48 VDC Output
Output Voltage adjustable
Power Good Signal
Low Ripple and Noise
Overload and Short-Circuit Protection
Parallel Operation possible
Worldwide Safety Approvals
Redundancy Module
3 Year Product Warranty
The TRACOPOWER TCL series are a family of DIN-Rail power supplies with an ex-
cellent price/performance ratio. With tightly regulated output voltage and high im-
munity against electrical disturbances on the mains they provide a reliable power
source for sensitive loads in industrial process controls, machine tools and other
equipment exposed to a difficult industrial environment. Compact size, light weight,
easy snap-on mounting on DIN-rails and the choice of two connection terminal
versions are other features of these power supplies. The TCL series complies with
all mayor safety standards for Europe (EN60950, EN50178), North America (UL/
cUL60950, UL508C listed) or elsewhere in the world (with CB-Report IEC60950).
Ordercode
Input Voltage
Output Power
*Output Voltage
Output Current
Connection
Range
max.
nom.
max.
TCL 024-105
5.1 VDC
4.0 A
TCL 024-112
24 W
12 VDC
2.0 A
TCL 024124
24 VDC
1.0 A
TCL 060112
12 VDC
4.0 A
Detachable Screw
TCL 060124
60 W
24 VDC
2.5 A
Terminal Block
TCL 060148
85 264 VAC
48 VDC
1.25 A
TCL 120112
Universal Input
120 W
12 VDC
8.0 A
TCL 120124
50 / 60 Hz
24 VDC
5.0 A
TCL 024124C
24 W
24 VDC
1.0 A
TCL 060112C
12 VDC
4.0 A
TCL 060124C
60 W
24 VDC
2.5 A
Cage-Clamps
TCL 060148C
48 VDC
1.25 A
TCL 120112C
120 W
12 VDC
8.0 A
TCL 120124C
24 VDC
5.0 A
Models
UL 60950
UL 508C
*Output adjustable
NEW
http://www.tracopower.com
Page 2 of 5
All specifications valid at nominal input voltage, full load and +25C after warm-up time unless otherwise stated.
Industrial Power Supplies
TCL Series
24120 Watt
Input Specifications
Input voltage range
85...264 VAC / 85...375 VDC
output derating at operation between 85...93VAC/85...130VDC:
15% for TCL 060 & TCL 120 models
20% for TCL 024-112 & TCL 024-124
30% for TCL 024-105
Input frequency
47 63 Hz
Harmonic limits
EN610000-3-2 Class A
Input current at full load (typ.)
115 VAC
230 VAC
TCL 24 models: 0.35 A
0.2 A
TCL 60 models: 1.2 A
0.6 A
TCL 120 models: 2.0 A
1.0 A
Recommended circuit breaker (characteristic C or slow blow fuse)
5.0 A
Output Specifications
Output voltage adj. range
5.1 VDC model: 5.0 5.25 VDC
(pot.meter on frontpanel)
12 VDC models: 12 15 VDC (12 - 16 VDC for TCL 024-112)
24 VDC models: 24 28 VDC
48 VDC models: 48 56 VDC
Output regulation (10 to 90% load variation)
2.5% (1% for TCL 60-112)
Ripple and Noise (20MHz Bandwidth)
< 50 mV pk-pk
Electronic short circuit protection
current limitation at 120 % typ
(constant current, automatic recovery
TCL 24 models: foldback, automatic recovery)
Parallel operation
output current characteristic suitable for
parallel operation of max. 5 units
Overvoltage protection, triggerpoint
5.1 VDC model: < 6.5 VDC
12 / 24 VDC models: < 40 VDC
48 VDC models: < 60 VDC
Hold-up time
115 VAC
230 VAC
min. 15 ms
min. 125 ms
Power good signal (TCL 60 & TCL 120 only)
trigger
output signal
point
(reference to Vout)
12 VDC models: >11V
11.0 V 1.0V / 60 mA max.
24 VDC models: >22V
22.0 V 2.0V / 30 mA max.
48 VDC models: >44V
44.0 V 4.0V / 15 mA max.
General Specifications
Temperature ranges
Operating
10 C...+70 C max.
Storage (non operating)
25 C...+85 C
Temperature derating
at 187...264 VAC or 265...375 VDC operation
1.7% /K above 50C
at 93...132 VAC or 130...187 VDC operation
1.1% /K above 40C
at 85...130 VDC operation
1.3% /K above 30C
Humidity (non condensing)
95 % rel. H max.
Temperature coefficient
0.02 % /K
Switching frequency
55 180 kHz depending on load
(frequency modulation)
Efficiency
88% typ.
Isolation
according to IEC/EN 60950, UL 60950,
UL 508, EN 50178, EN 60204, EN 61558-2-8
Reliability, calculated MTBF @ 25C
TCL 24 models: >2.68 Mio h
(according to IEC-1709)
TCL 60 models: >2.94 Mio h
TCL 120 models: >1.62 Mio h
http://www.tracopower.com
Page 3 of 5
All specifications valid at nominal input voltage, full load and +25C after warm-up time unless otherwise stated.
General Specifications
Safety standards
IEC 60950, EN 60950 (output SELV),
UL 60950, UL 508, EN 50178,
EN 60204, EN 61558-2-8.
- NEC class 2 (TCL 60 models only)
Safety approvals (TCL 24 models pending)
UL/cUL 60950 recognized, File E181381
UL 508C listed, File E210002
CB-Report per IEC 60950
Electromagnetic compatibility (EMC), Emissions
EN 61000-6-3
Electromagnetic compatibility (EMC), Immunity
EN 61000-6-2
Safety class
degree of protection class 1
Case protection
IP 20 (IEC 60529)
Enclosure material
plastic FR2010-110C (UL 94V-0 rated)
Mounting
35 mm DIN-rails as per EN 50022-35x15/7.5
(snap-on with self-locking spring)
Adapter for Wall-/Chassi Mounting (included)
Options
output characteristic optimized for battery
charging available on request
Industrial Power Supplies
TCL Series
24120 Watt
TCLREM240 Redundancy Module
This module enables redundant operation of any two TCL models by decoupling
the 2 power supplies. It can also be used to separate sensitive loads from the main
power source.
Order code
Inputs
Vin
Max power
per input
Output voltage
Output current
max.
Connection
TCLREM240
2 x 5...60 VDC
144 W
Vin 0.9 VDC
8 A
detachable screw
terminal block
Models
Specifications
Operating temperature
10C...+70C max. (14F...+158F)
derating above 40C (104F): 1.5%/K
Electromagnetic compatibility
in correspondence to connected units
(no internal switching device)
Dimensions
same as model TCL 24 (see page 4)
http://www.tracopower.com
Page 4 of 5
All specifications valid at nominal input voltage, full load and +25C after warm-up time unless otherwise stated.
27
(1.06)
2.2
(0.09)
100.0
(3.94)
75.0
(2.95)
DC-ON LED
Output voltage
adjust
INPUT
1 2 3
OUTPUT
1 2
Outline Dimensions mm (inches)
Industrial Power Supplies
TCL Series
24120 Watt
TCL 24 and TCL-REM240
TCL 60
Weight: 140g (4.9 oz)
Weight: 265g (9.4 oz)
Output
Innput
1 +Vout
1 AC Ground
2 Vout
2 Neutral
3 Live
Output
Innput
1 +Vout
1 AC Ground
2 +Vout
2 Neutral
3 Vout
3 Live
4 Vout
5 Power Good
75.0
(2.95)
100.0
(3.94)
3.2
(0.13)
45
(1.77)
DC-ON LED
Output voltage
adjust
OUTPUT
1 2 3 4 5
INPUT
1 2 3
Tolerances: 0.5mm (0.02)
Page 5 of 5
Specifications can be changed without notice
Outline Dimensions mm (inches)
Jenatschstrasse 1 CH-8002 Zurich Switzerland
Tel. +41 43311 4511 Fax +41 43311 4545 info@traco.ch www.tracopower.com
Industrial Power Supplies
TCL Series
24120 Watt
TCL 120
Weight: 440g (15.5 oz)
Output
Innput
1 +Vout
1 AC Ground
2 +Vout
2 Neutral
3 Vout
3 Live
4 Vout
5 Power Good
Tolerances: 0.5mm (0.02)
Wall Mounting Bracket
Instead on a DIN-rail, the module can be
easily mounted on a chassis or wall with help of
a mounting bracket which is supplied as standard
with each Power Supply
75.0
(2.95)
100.0
(3.94)
3.2
(0.13)
85
(3.35)
DC-ON LED
Output voltage
adjust
OUTPUT
1 2 3 4 5
INPUT
1 2 3
DIN rail mounting hooks 20mm (0.79) wide
Rev. 07/05