ChipFind - документация

Электронный компонент: TIS150-124

Скачать:  PDF   ZIP
http://www.tracopower.com
Page 1
Industrial Power Supplies
TIS Series 75 - 600 Watt
Features
Switch mode power supplies for
DIN-rail mounting
4 power ranges with 3, 6, 12 and 24 A
output current (24 VDC models)
Selectable 115/ 230 VAC input
Very low ripple and noise
EMI complies with EN50081-2 and
EN50082-2
Conducted EMI to EN55011 class B
For system operation available with
built-in functions:
RED:
Redundancy module for N+1
systems with true current sharing.
SIG:
Signal module with AC-Power-
fail, DC- OK Signal and
external ON/OFF control
UDS:
DC-UPS module for uninter-
ruptable battery backed-up
power systems.
Worldwide Safety Approvals
Easy snap-on mounting on DIN-rails
or chassis mounting
2 Year Product Warranty
The switching power supplies of the TIS series have been particulary de-
signed for applications in industrial process control systems and machine
tools. Excellent specifications and high immunity against electrical distur-
bances guarantee reliable power for sensitive loads in rugged industrial
environments. With help of optional function modules specific requirements
for system applications can be met by a standard product. With the UDS
module the power supplies can be extended to a perfect DC-UPS with auto-
matic battery- backup. This function is very often required in applications
where a time delayed shutdown of a system is necessary. To monitor and
control the power supply a signal module can be installed. For parallel
operation with active power sharing a redundancy option is available. This
flexibility makes the TIS series power supplies a cost effective solution for
many industrial applications.
Models
Ordercode
Input Voltage
Output Power
Output Voltage
Output Current
(includes terminal plugs)
max.
nom.
max.
TIS 75-112
115 / 230 VAC
12 VDC
6.0 A
TIS 75-124
selectable
75 W
24 VDC
3.0 A
TIS 75-148
48 VDC
1.5 A
TIS 150-124
115 / 230 VAC
150 W
24 VDC
6.0 A
TIS 150-148
selectable
48 VDC
3.0 A
TIS 300-124
115 / 230 VAC
24 VDC
12 A
TIS 300-148
selectable
300 W
48 VDC
6.0 A
TIS 300-172
72 VDC
4.2 A
TIS 500-124
230 VAC
500 W
24 VDC
20 A
TIS 600-124
24 VDC
24 A
TIS 600-128
115 / 230 VAC
600 W
28 VDC
22 A
TIS 600-148
selectable
48 VDC
12 A
TIS 600-172
72 VDC
8.5 A
TIS 300-124 DCI
300 - 800 VDC
300 W
24 VDC
12 A
http://www.tracopower.com
Page 2
All specifications valid at nominal input voltage, full load and +25C after warm-up time unless otherwise stated.
Industrial Power Supplies
TIS Series 75-600 Watt
Input Specifications
Input voltage range TIS 75, TIS 150, TIS 300, TIS 600
93 132 VAC / 187 264 VAC
TIS 500
187 264 VAC
TIS 300 DCI
300 800 VDC
Input frequency
47 63 Hz
Input current at full load (typ.)
115 VAC
230 VAC
TIS 75
1.7 A
0.9 A
TIS 150
3.0 A
1.7 A
TIS 300
5.4 A
3.3 A
TIS 500
5.5 A
TIS 600
10.5 A
6.4 A
Inrush current (< 2 ms)
115 VAC
230 VAC
TIS 75
< 16.5 A
< 33 A
TIS 150
< 35 A
< 70 A
TIS 300
< 35 A
< 70 A
TIS 500
< 70 A
TIS 600
< 70 A
< 80 A
Output Specifications
Output voltage adj. range
12 VDC models
12 14 VDC
24 VDC models
24 28 VDC
28 VDC models
28 32 VDC
48 VDC models
48 52 VDC (48 55 VDC on request))
72 VDC models
60 76 VDC
Regulation Input variation
0.2 % max.
Load variation (10 90 %) TIS 75, TIS 150
1.0 % max.
TIS 300, TIS 500, TIS 600
0.3 % max.
( 1.5 % in parallel operation)
Ripple and Noise (20MHz Bandwidth)
< 50 mV pk-pk
Electronic short circuit protection
current limitation at 110 % typ.
(constant current, automatic restart)
Overvoltage protection, triggerpoint at
140 % typ. Vout nom.
Hold-up time
115 VAC
230 VAC
TIS 75 ... TIS 300
min. 25 ms
min. 30 ms
TIS 500
min. 40 ms
TIS 600
min. 15 ms
min. 25 ms
http://www.tracopower.com
Page 3
All specifications valid at nominal input voltage, full load and +25C after warm-up time unless otherwise stated.
General Specifications
Temperature ranges Operating (ambient temp.)
25 C...+70 C max.
Derating above 50 C
2% /C
Storage (non operating)
25 C...+ 85 C
Humidity (non condensing)
95 % rel H max.
Temperature coefficient
0.02 % / C
Switching frequency
80 kHz typ. (Pulswidth modulation)
Efficiency
TIS 75 ... TIS 300
85 % typ.
TIS 500
90 % typ.
TIS 600
88 % typ.
Isolation
according to EN 60950, UL 1950, UL 508C
Reliability, calculated MTBF (MIL-HDBK-217 E) TIS 75 /150
450000 h @ +25C/ 420000 h @ +25C
TIS 300 /500
360000 h @ +25C/ 340000 h @ +25C
TIS 600
300000 h @ +25C
Safety standards
IEC 60950, EN 60950 (SELV),
UL/cUL 1950, UL 508C
Safety approvals
UL/cUL 1950 recognized, File E18138
UL/cUL 508C listed, File E210002
UL/cuL 1604 listed, File E213613 (Class I,Division
2, Groups A, B, C and D hazardous locations)
CB-Scheme
Electromagnetic compatibility (EMC), Emissions
EN 50081-1 / EN 50081-2
Conducted RI suppression on input
EN 55011 class B, EN 55022 class B,
FCC part 15, level B
Radiated RI suppression
EN 55011 class A, EN 55022 class A,
FCC part 15, level A
Electromagnetic compatibility (EMC), Immunity
EN 50082-2
Electrostatic discharge (ESD)
IEC / EN 61000-4-2 4 kV / 8 kV
Radiated RF field immunity
IEC / EN 61000-4-3 10 V / m
Electrical fast transient / burst immunity
IEC / EN 61000-4-4 2 kV
Surge immunity
IEC / EN 61000-4-5 2 kV / 4 kV
Immunity to conducted RF disturbances
IEC / EN 61000-4-6 10 V
Power frequency field immunity
IEC / EN 61000-4-8 30 A / m
Safety class
Degree of Protection 1 (IEC 536)
Case protection
IP 20 (IEC 529)
Environment
Vibration
IEC 60068-2-6,1 gn, 200 sweeps, each axis
Shock
IEC 60068-2-27, 15 gn, 11 ms, each axis
Enclosure material
Aluminium (chassis) / stainless steel (cover)
Mounting (snap-on with selflocking spring)
for 35 mm DIN-rails as per EN 50022
Connection
Plugable screw terminals (plugs included)
(TIS 600: screw terminal blocks)
Industrial Power Supplies
TIS Series 75-600 Watt
http://www.tracopower.com
Page 4
Specifications can be changed without notice
Optional Mounting Systems Dimensions mm (inches)
Power Supplies with Redundancy Function
With this option a parallel operation of up to 5 units is possible. Decoupling diodes and current share lines allow to build
true N +1 redundant systems with active current sharing for all units. This function also includes an alarm relay to signal
a single unit failure.
This option is available for TIS 150 W, TIS 300 W and TIS 600 W models. Please note: A combination with other
options is not possible.
Models
Ordercode
Input Voltage
Output Power
Output Voltage
Output Current
(includes terminal plugs)
max.
nom.
max.
TIS 150-124 RED
115 / 230 VAC
150 W
24 VDC
6.0 A
TIS 150-148 RED
selectable
18 VDC
12 A
TIS 300-124 RED
115 / 230 VAC
300 W
24 VDC
12 A
TIS 300-148 RED
selectable
48 VDC
6.0 A
TIS 600-124 RED
115 / 230 VAC
600 W
24 VDC
24 A
TIS 600-148 RED
selectable
48 VDC
12 A
Industrial Power Supplies
TIS Series 75-600 Watt
Specifications
Raiting per relay contact
60 VDC /0.36 A max.
I-Sense
Regulator
L
Con1
Pin3
N
115/230V
AC
Con1
Pin1
AC
Con1
Pin2
DC
Common
Unit
OK
Unit OK
Con3 - Pin1
Bus
Indicator
Con2 - Pin1/2
Con2 - Pin3/4
V-Sense
+Vout
Current
Share-
line
Unit OK
Con3 - Pin4
Con3 - Pin3
Con3 - Pin2
-Vout
24/48VDC
http://www.tracopower.com
Page 5
All specifications valid at nominal input voltage, full load and +25C after warm-up time unless otherwise stated.
Power Supplies with Powerfail Functions
These models provide 3 functions required in many process control system applications:
AC-Powerfail signal (relay contact)
DC-OK signal (relay contact)
Remote ON/OFF
Models
Ordercode
Input Voltage
Output Power
Output Voltage
Output Current
(includes terminal plugs)
max.
nom.
max.
TIS 150-124 SIG
115 / 230 VAC
150 W
24 VDC
6.0 A
TIS 150-148 SIG
selectable
48 VDC
3.0 A
TIS 300-124 SIG
115 / 230 VAC
300 W
24 VDC
12 A
TIS 300-148 SIG
selectable
48 VDC
6.0 A
TIS 600-124 SIG
115 / 230 VAC
600 W
24 VDC
24 A
TIS 600-148 SIG
selectable
48 VDC
12 A
Industrial Power Supplies
TIS Series 75-600 Watt
Specifications
DC-OK signal trigger point Models with 24 Vout
> 22.8 VDC 0.5 V
relay B closed (pin 4 pin 3)
Models with 48 Vout
> 45.6 VDC 1.0 V
relay B closed (pin 4 pin 3)
AC-Powerfail signal
Vin < 93 resp. < 187 VAC relay A closed (pin 7 pin 6)
Raiting per relay contact
60 VDC /0.36 A max.
Remote
ON/OFF
L
115/230V
AC
Con1
Pin1
N
Con1
Pin2
Con1
Pin3
AC
DC
Mains
Fail
Detection
Mains OK
Remote
ON/OFF
+Vout
Con2 - Pin3/4
-Vout
24/48VDC
Common
AC-Powerfail
Con3 - Pin2
Con3 - Pin7
Con3 - Pin6
Con2 - Pin1/2
Output
OK
DC-OK
Detection
DC-OK
Common
DC-OK
DC-OK
Con3 - Pin5
Con3 - Pin4
Con3 - Pin3
+
-
Con3 - Pin1
(Relay A)